Dedicated Line - Things to consider
@whart . Thanks for the kind words. Best regards, Jim  
Advantage using one electrical leg for audio system?
then is the way OP did it   preferable to running two circuits of 10-2 with two separate neutrals? NO.. Two 10/2 with ground Romex cables fed from single pole breakers fed from the same Line, Leg,... IS Much, Much, better than what you have ... 
Advantage using one electrical leg for audio system?
If it bothers you, an electrician can probably move wires around in your panel to keep both lines on the same leg. an electrician can probably move wires around in your panel to keep both lines on the same leg. No he can’t... The OP has a 3 ... 
Does a higher gauge electrical wire impact voltage level?
Most amplifiers are "unregulated." Meaning long term (several seconds) changes in the AC line will make it to the amplifier voltage rails. So if your DC rails are +- 50V with 120VAC input, they will vary in proportion to input. They could be 45V ... 
Hum on Tube Amp - Can't find source
I have had good luck with The Tube Store over the years.  
Hum on Tube Amp - Can't find source
@ervikingo The 7044 tube is the Driver tube... I would strongly suggest you tell the vendor you buy them from you need each section of the Triode tightly, closely, matched. Pay extra for each tube if you have to. I doubt you will get that from... 
Hum on Tube Amp - Can't find source
  @holmz        you beat me to it...   @dpop It kind of sounds like a low frequency motorboating oscillation. This may be off the wall, but I seem to remember reading a thread several years ago, can’t remember if it was on Agon or AA wh... 
Sharing ground wire between two dedicated circuits
emergingsoul OP 468 posts 12-08-2022 at 02:39pm So it sounds like having an insulated ground back to the panel doesn’t matter. What about interference, all that noise and crap being diverted back to the panel via ground. Why wo... 
Sharing ground wire between two dedicated circuits
@emergingsoul said: Idea has been proposed to share the insulated ground from the 10/3 wire with the other 10/2 dedicated circuit. Achieves the same thing at a lot less cost? Does this make sense? No not to me it doesn’t. Per NEC the EGC, "(Eq... 
Outlet - Shunyata vs Hubble 20 amp
@dekay said: I recall that Albert also used 5262 & 5362 as a base for the Porterport.  Ya, I recall after Hubbell changed the HBL8300H Hospital Grade outlet Albert had to find something else that sounded as good. He ended using the Hubbell... 
Outlet - Shunyata vs Hubble 20 amp
@dekay said: I use both 5362 and 8300. Two 5362’s in wall and 8300’s in my power conditioners. They were all manufactured 20+ years ago. The HBL5362 Extra Heavy duty industrial deep Body outlets are still the same. https://www.graybar.com/h... 
Outlet - Shunyata vs Hubble 20 amp
stringreen 6,206 posts 11-30-2022 at 01:43pm  The best one I found after trying many.....Maestro @stringreen  Does it look like this?    
Outlet - Shunyata vs Hubble 20 amp
  @erik_squires Said: What exactly is the alternative and is it rated for residential use?? Yes it meets, exceeds, NEC requirements. Constructional Feature: Impact Resistant, Tamper Resistant   Also, nickel plated steel ... 
Outlet - Shunyata vs Hubble 20 amp
  https://www.leviton.com/en/products/8200-sgw Not a good choice, imo. From the specs: Line Contacts: Nickel Plated Phosphor Bronze Strap Material: Nickel Plated Steel ^ ^ ^ ^ Ferrous steel Not Good.   / / / / / / Better Leviton outlet: ... 
Outlet - Shunyata vs Hubble 20 amp
onlinecomponents.com - Octopart Go to page 6: HBL5362 outlet. Brass contacts. Brass supporting back strap. Not nickel plated... / / Next go to page 8: HBL8300 Hospital Grade outlet. Nickel plated contacts. Nickel plated supporting back strap.