Amp Shutting Down, need help
Sailcappy,So during the tests on the 15 amp circuits not one of 15 amp breakers tripped. But the 15 amp magnetic breaker on the Cary amp did......And of all the 5 circuits the amp was tested on the odds are great that at least 2 were on the other ... 
Amp Shutting Down, need help
Its easy enough to test for. There is someone on this forum who makes AC extension outlets that have the DC Blocker built in. Just use one of those and you would know if that's what it is.08-22-12: AtmasphereAtmasphere,Agree....The Agon's members ... 
Amp Shutting Down, need help
Sailcappy,No I would not use the lightning bare 4/0 ground wire for an auxiliary equipment ground..... That could open up a whole new can of warms.• I attached a three way strip I had lying around into the end of the extension cord. I then plugged... 
Amp Shutting Down, need help
Sailcappy,I forgot to ask. Is your friend, that works for the power company, an Electrical Engineer? An electrical technician?The reason I ask is your friend qualified, confident, to preform work inside the electrical panel of your apartment?Nothi... 
Amp Shutting Down, need help
Sailcappy,Thanks for the detailed start up procedure.1. Prior to doing anything I check that the rear breaker On/Off switch is set to the off position and the front Standby/Active switch is set to the Standby position......."and the front Standby/... 
Amp Shutting Down, need help
Look! Every time I get close to addressing and finishing a few paragraphs in response, all you guys quickly sneak in answers and more questions! So, I'll just sit patiently in the corner with a "filthy bed-wetter" sign on and wait fer a bit. :-D 0... 
Amp Shutting Down, need help
Hi Swampwalker,I believe when the amp is first powered up using the switch breaker on the rear panel of the amp the breaker holds in the standby mode..... The proper shut down procedure is to first push the power button on the front panel of the a... 
Amp Shutting Down, need help
Hi Al,4. Not sure what you are asking the 15amp breaker which is the on/off switch for the breaker trips it to the off position when I noticed this drop. Remember this happens after i go from standby mode to Active mode.08-21-12: SailcappyFrom wha... 
Amp Shutting Down, need help
Hi Al,By chance did you read the Cary owner manual?http://caryaudio.com/pdfs/manuals_2012/Model7.250_manual.pdfCAUTION.If the unit is in active mode and power is removed, it will remain activated when power is restored.>>>So it looks to m... 
Amp Shutting Down, need help
2. The 50’ extension cord has the following information imprinted on the jacket 16/3. I assume that means 16 gauge times three wires.Correct...The cord impedance is limiting inrush current through the magnetic breaker of the Cary amp when the amp ... 
3 preamps with transformer hum, DC on the line?
Gbart,Thanks for the info. I printed out your post, with email address and links, for future reference.I suggest others do the same in case the post disappears..... Sure do miss the old Agon email member feature.....Jim 
3 preamps with transformer hum, DC on the line?
Airkitty,If you posted an email address Gbart might contact you..... Not sure what he charges to build a DC blocker.. 
Amp Shutting Down, need help
Hi Al,I hoped you would see my post.As Metro04 pointed out more than likely the electrical equipment grounding conductor for the branch circuits is the metallic conduit, boxes, and fittings. Back in the 1970s that was acceptable per NEC and more t... 
Amp blowing fuses
...... one is blowing 3A slo-blo fuses instantly on powerup.I've thought about trying a 4A fuse but ......Rawinsonde Sounds like a dead short. I would not increase the fuse size.Take the amp to a repair shop..... Possible problem could be a shorte... 
Amp Shutting Down, need help
Things known.From the Cary's owners manual.*Uses a soft start circuit. That limits inrush current.*Has built in DC offset filter protection. (That would be after the magnetic circuit breaker)*Uses a magnetic trip circuit breaker. (Would not be my ...