Please assure me I'm not going to burn my house down.
toddverrone OP 121 posts                                             02-20-20172:26pm@jea48 check this: http://www.southwire.com/ProductCatalog/XTEInterfaceServlet?contentKey=prodcatsheet393That is the wire I used. The outer jacket is high temp ... 
Can't tell,if my house is properly grounded
One more test.With only the preamp connected to the power amp, TT not connected to the inputs of the preamp, unplug the preamp from the AC power.  Turn on power amp and check for the buzz/hum. 
Can't tell,if my house is properly grounded
last_lemming OP  265 posts                                              02-20-2017 10:46amWhat TT are you using? Cartridge? I have a Dynavector 20x2L, and the cables are Cardas Clear Light. They have never given me trouble before. I don’ t know i... 
Please assure me I'm not going to burn my house down.
The actual insulation around the wire itself is Teflon... I think the blue outer sleeve is PVC. Not from my experience. The outer jacket is Teflon and the insulation around the wire is PVC. It is the outer jacket of the cable that is plenum rated... 
Can I use this amp in my house?
sbank,From the manual, Full Power Balanced Power Amplifiers600, 300, 200 Stereo650M, 350M, 250M Monaural AC Power ConsiderationsFor best performance, a dedicated AC power line rated at a minimum of fifteen amps is recommended for each amplifier. ... 
Can I use this amp in my house?
sbank,What size of amp/s are you looking at? I should have mentioned in my last post, just because the manufacture installs a 20 amp IEC inlet on the back of his equipment doesn't mean he had to do it to meet bare minimum electrical industry stand... 
Can I use this amp in my house?
But I will add that I just got a Krell FPB-300, with a 20amp plug, and it came with a cord that has the 20amp connector for the amp on one end, and the other end has a standard 15 amp plug on it. Crazy ain’t it? And it might even be a Listed powe... 
Can I use this amp in my house?
lak,Thank you for the kind words. 
Can I use this amp in my house?
Hodu,At 200 watts per channel amp if you will be pushing the amp with high dynamic music don't let the electrician talk you into using #12awg wire. #12 is bare minimum for a 20 amp circuit. Stick to your guns and tell him #10 wire.You want the mai... 
Can I use this amp in my house?
If the plug on the power cord is a NEMA 5-20P 125V 20 amp rated plug then per NEMA, UL, and NEC code the amplifier continuous FLA (Full Load amps) cannot exceed 16 amps.20 amps X 80% = 16 amps. Continuous is 3 hours or more.Per NEC electrical safe... 
Qs about Bias
Like others have said the amp needs to be warmed up before attempting to bias.From ARC Bias instructions: For best results, operate and adjust the Reference110 at120VAC. Adjustment must be made under zero-signal conditions after at least 15-20 min... 
Marantz Pure Direct modes
Owner manualhttp://m.us.marantz.com/DocumentMaster/US/UD7007OwnersManualinEnglish.pdf 
KT 91
The KT91 must really be an oddball tube number. Doing a search I couldn’t find any data sheet on it. I did find an Ebay listing for the tube. The guy says he used the 6550 settings on his B&K707 to test the tube.http://www.ebay.com/itm/Vintage... 
Environmental Potentials whole house surge protection, can I get your opinions?
westom,LOL,You just ramble on and on saying the same things over and over.As for my posts on this thread I believe I answered all the OP’s questions and concerns accurately. Starting with SPDs and the importance of the integrity of the electrical ... 
Environmental Potentials whole house surge protection, can I get your opinions?
westom,What is the purpose of the National Electrical Code? The purpose of the National Electrical Code is the practical safeguarding of persons and property from hazards arising from the use of electricity. Not your opinion or your interpretati...