Hey Guys,

 

When building a dedicated electrical circuits is it better to add to my current box or add a sub panel?  Pro's and con's?

 

Current plan is 10/2 w/ Shunyata outlets.

 

Thank you

Jim

offbrandracing

Adding another panel adds additional connections, another expensive panel, and an additional circuit breaker. The only advantage would be if the wire run is very long, 100 ft or more, in which case it would allow use of much larger gauge wire for the majority of the run with the panel located near the system. Any other situation and it is worse not better. 
 

Muliple lines runs the risk of ground loops. Even if this is avoided every wire is an antenna bringing RFI into the system. So one single dedicated line is the way to go. 
See Michael Fremer talking about his system when he says the same thing. Years ago. People are slow to adopt new information. 

I use one direct run of Romex 8/2. I found it easier to handle as it’s stranded compared to the 10 gauge solid conductors. The wire wasn’t too thick and fitted into 20amp hospital grade receptacles.