**IF** the dedicated ground rod is all the electrician used for the ground for the duplex receptacle outlets then there is not a safety equipment ground connection back to the electrical service electrical panel equipment ground.
What you have is no different than using ground cheaters at the wall outlets that your audio equipment that use the equipment ground for electrical safety.
Actually if that is what the electrician did what you have is worse than just using ground a cheater to lift the safety equipment ground at the wall outlets.
If you have a multi meter set the meter to auto AC volts. measure for voltage from the neutral contact to the equipment ground contact at one of the wall outlets. If the branch circuit wiring equipment grounding conductor is connected to the ground terminal on the outlet you should measure zero volts nominal. The reason the voltage should read zero volts nominal is because the equipment grounding conductor is connected to the grounded electrical service neutral conductor. That is the common ground point for the building structure.
**IF** the dedicated ground rod is all the electrician used for the ground for the duplex receptacle outlets then there is not a safety equipment ground connection back to the electrical service electrical panel equipment ground.
What you have is no different than using ground cheaters at the wall outlets that your audio equipment that use the equipment ground for electrical safety.
Actually if that is what the electrician did what you have is worse than just using ground a cheater to lift the safety equipment ground at the wall outlets.
If you have a multi meter set the meter to auto AC volts. measure for voltage from the neutral contact to the equipment ground contact at one of the wall outlets. If the branch circuit wiring equipment grounding conductor is connected to the ground terminal on the outlet you should measure zero volts nominal. The reason the voltage should read zero volts nominal is because the equipment grounding conductor is connected to the grounded electrical service neutral conductor. That is the common ground point for the building structure.