Grounding Metal Outlet Boxes and Isolated Ground Receptacles


Just installed six really nice separate dedicated 20 amp lines (with 6 awg) for my new dedicated listening room.  Decided to use heavy metal outlet boxes so that I could make my six Furutech Receptacles as strong and sturdy as possible.  I also had my electrician run 4-wire 6 agw to the boxes so that we could have one ground wire to the metal receptacle box and then a separate ground wire to the isolated ground screw on the Furutech.

I sent some photos of the setup to a friend of mine (who just happens to be an electrical engineer) and he raised an the issue that since my Furutech Receptacles are metal and they will be screwed into the metal box with metal screws, then we have effectively now tied the two separate grounds together!  Help!  Is that a bad idea?   Is having the box and receptacle setup in this way going to cause issues once my gear is in place; ground loop hums, etc?






stickman451
The average length of the six dedicated runs is approx 30 feet.  The room is 29' L x 21'-10" W.  The longest two runs are about 36 ft from the front wall back to the sub panel in the room.  The shortest run is about 25' from the sub panel.  

The sub panel is a GE PowerMark Gold.

All of the six 6awg dedicated lines will be on the same phase in the sub panel.  Lighting and standard wall outlets will be on the opposite phase. 

The sub panel in my room is approx 60 ft from the main panel (which is in the car garage).  

Not sure on your other questions but should get those answers tomorrow when i speak with the electrician.

The Furutech outlets are Not Isolated Ground for sure.  I checked the continuity with a Radio Shack tester and the ground screw is connected to the outlets metal mounting brackets.

Main issue is I do not want to create an electric hazard (pretty sure my electrician is very capable) and I do not want to create a bunch of ground loop issues!


Main issue is I do not want to create an electric hazard (pretty sure my electrician is very capable) and I do not want to create a bunch of ground loop issues!

From the description of the wiring materials and wiring methods used in your posts everything meets or exceeds electrical safety code. At least NEC. I would imagine your electrician followed any local electrical codes that differed from NEC.

As for any ground loop problems, just my opinion, your branch circuits runs are too short to cause any ground loops. If they were long, say 60ft to a 100ft, the 6-3 with ground may have been a problem as I described in an earlier post. Especially paralleling the bare equipment ground wire with one of 3 insulated conductors of the cable.

I wouldn’t be surprised though if the electrician doesn’t rework the equipment ground wiring in the six wall rough-in outlet boxes after you tell him the 6 duplex receptacles are not IG grounding type duplex receptacles. He has to hang his name and reputation on the job when he’s done.

As far as the way I would do it now, knowing the duplex receptacles are not IG, I would cap off the insulated wire in the box and just leave it as a spare unused wire. I would pigtail the bare equipment ground with two pigtails. One to bond the metal box and the other to connect to the ground terminal on the duplex receptacle.

(Just going from memory the construction of 6-3 with ground NM-B cable (Romex), the bare ground wire is in the middle of the three twisted insulated wires. For me anyway, that lessens any chance of an induced voltage transfer from the hot and neutral current carrying conductors onto the equipment ground wire.)

As for what to do with the spare capped off wire of the 6-3 with ground Romex at the electrical panel end? Normally it would be capped off and left laying in the bottom of the panel for future....... But in this instance it is part of a cable assembly that will be feeding an audio system. An audio system where the user has spent big bucks in hopes of getting the lowest noise floor possible. I would wonder if the floating insulated wire might act as an antenna and pick up air born RFI. I would probably connect the end at the panel to the ground bar. Nothing wrong with that as far as a code issue. Ask your electrician if he has a problem with it.

It would be nice to hear from Al, (almarg), what he thinks. Would he connect the end of the spare insulated wire at the electrical panel to the ground bar, or leave it floating above ground?

Jim

.

Jim,

i appreciate you giving me your thoughs on this!  Thanks!   I'd also be curious on almarg thoughts on this; he know's his stuff!

I will run the options that you suggested by my electrician and see what he says.  One option we are looking at is to pull out the metal boxes, put in a high quality plastic or fiberglass box and elimintate any ground to the box.  The extra insultated ground wire would just be left unused.


One option we are looking at is to pull out the metal boxes, put in a high quality plastic or fiberglass box and elimintate any ground to the box.

I don’t think the electrician will find a plastic or fiber receptacle outlet rough-in box big enough for 6-3 with ground that will meet NEC for the conductor fill requirements. (2014 NEC 314.16) That’s why, I believe, the electrician used a steel square box with a single gang raised device cover. I personally would leave what you have now. If the receptacle supporting back strap was made of steel then you might hear a difference in sound. The supporting back strap on the Furutech is not made of ferrous steel. What type of duplex cover plate are you going to use? THAT can change the sound of your audio system!



As you suggested We may just leave it as is.

Would love to use the Furutech covers, but man are they pricey!! Got any recommendations?

BTW, went momentarily crazy this weekend and bought a Kronos Limited turntable; beautiful table!!!